R-410AZR SERIES 15 - 25 Ton60 Hertz 275864-YIM-C-0910TABLE OF CONTENTSGeneral . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
275864-YIM-C-091010 Johnson Controls Unitary ProductsFigure 6: ZR180-300 Unit Dimensions Rear ViewNOTE: Units are shipped with the bottom duct openin
275864-YIM-C-0910Johnson Controls Unitary Products 11Figure 7: ZR180-300 Unit Dimensions Rain HoodNote: ELEC/ELEC Models: Units and ductwork are appro
275864-YIM-C-091012 Johnson Controls Unitary ProductsFigure 8: ZR180-300 Roof CurbDuctworkDuctwork should be designed and sized according to the metho
275864-YIM-C-0910Johnson Controls Unitary Products 13Figure 9: Fixed Outdoor Air DamperCondensate DrainPlumbing must conform to local codes. Use a sea
275864-YIM-C-091014 Johnson Controls Unitary Productselectrically grounded in accordance with NEC and CEC as specified above and/or local codes.Voltag
275864-YIM-C-0910Johnson Controls Unitary Products 15Figure 11: Field Wiring Disconnect - Cooling Unit With/Without Electric HeatThermostat WiringThe
275864-YIM-C-091016 Johnson Controls Unitary ProductsFigure 12: Typical Field WiringTHERMOSTAT 1TERMINALS( RCB )REHEATCONTROL BOARDRCRHY1Y2W1W2GCX1X3X
275864-YIM-C-0910Johnson Controls Unitary Products 17Table 8: Electrical Data ZR180-300 - Standard Drive Without Powered Convenience Outlet Size(Tons
275864-YIM-C-091018 Johnson Controls Unitary Products ZR180-300 - Standard Drive With Powered Convenience Outlet Size(Tons)VoltCompressors(each)OD Fa
275864-YIM-C-0910Johnson Controls Unitary Products 19 ZR180-300 - High Static Drive Without Powered Convenience Outlet Size(Tons)VoltCompressors(each
275864-YIM-C-09102 Johnson Controls Unitary ProductsGeneralYORK® Model ZR units are either single package air conditions equipped with optional factor
275864-YIM-C-091020 Johnson Controls Unitary Products ZR180-300 - High Static Drive With Powered Convenience Outlet Size(Tons)VoltCompressors(each)OD
275864-YIM-C-0910Johnson Controls Unitary Products 21ZR300 - Low Static Drive Without Powered Convenience Outlet Size(Tons)VoltCompressors(each)OD Fa
275864-YIM-C-091022 Johnson Controls Unitary ProductsTable 9: ZR180-300 Physical Data ComponentModelsZR180 ZR240 ZR300Nominal Tonnage 15 20 25ARI COO
275864-YIM-C-0910Johnson Controls Unitary Products 23Optional Electric HeatThe factory-installed heaters are wired for single point power supply. Powe
275864-YIM-C-091024 Johnson Controls Unitary ProductsOptional Gas HeatThese gas-fired heaters have aluminized-steel or optional stainless steel, tubul
275864-YIM-C-0910Johnson Controls Unitary Products 25Gas ConnectionThe gas supply line can be routed within the space and roof curb, exiting through t
275864-YIM-C-091026 Johnson Controls Unitary ProductsCheck all connections for leaks when piping is completed using a soap solution. NEVER USE A FLAME
275864-YIM-C-0910Johnson Controls Unitary Products 27the “A”, “B”, “C” or “D” setting corresponding to the lettered curve of the Enthalpy Set Point Ad
275864-YIM-C-091028 Johnson Controls Unitary Products• RH - a 0-10 VDC analog input provided by a field-installed return air relative humidity sensor
275864-YIM-C-0910Johnson Controls Unitary Products 29BAS-Ready VFDFactory-installed VFD is also available with 'BAS-ready' models. Terminal
275864-YIM-C-0910Johnson Controls Unitary Products 3Wear safety glasses and work gloves. Use quenching cloth and have a fire extinguisher available du
275864-YIM-C-091030 Johnson Controls Unitary ProductsFigure 16: Enthalpy Set Point ChartFigure 17: Honeywell Economizer Control W721240(4)70(21)50(10)
275864-YIM-C-0910Johnson Controls Unitary Products 31PhasingYork® Model ZR units are properly phased at the factory. Check for proper compressor rotat
275864-YIM-C-091032 Johnson Controls Unitary ProductsFigure 19: Altitude/Temperature Correction FactorsThe examples below will assist in determining t
275864-YIM-C-0910Johnson Controls Unitary Products 33Drive Selection1. Determine side or bottom supply duct application.2. Determine desired airflow3.
275864-YIM-C-091034 Johnson Controls Unitary ProductsTable 15: Air Flow Performance - Side Duct ApplicationZR180 (15 Ton) Side DuctAir Flow(CFM)Availa
275864-YIM-C-0910Johnson Controls Unitary Products 35ZR300 (25 Ton) Side DuctAir Flow(CFM)Available External Static Pressure - IWG10.4 0.6 0.8 1.0 1.2
275864-YIM-C-091036 Johnson Controls Unitary ProductsTable 16: Air Flow Performance - Bottom Duct ApplicationZR180 (15 Ton) Bottom DuctAir Flow(CFM)Av
275864-YIM-C-0910Johnson Controls Unitary Products 37ZR300 (25 Ton) Bottom DuctAir Flow(CFM)Available External Static Pressure - IWG10.4 0.6 0.8 1.0 1
275864-YIM-C-091038 Johnson Controls Unitary ProductsAir BalanceStart the supply air blower motor. Adjust the resistances in both the supply and the r
275864-YIM-C-0910Johnson Controls Unitary Products 39Supply Air Drive AdjustmentThe RPM of the supply air blower will depend on the required CFM, the
275864-YIM-C-09104 Johnson Controls Unitary ProductsNomenclatureZ R 180 N24 A 2 A AA 1 0 1 2 4 AZ = A/C, Single Pkg., R-410AProduct CategoryAirflow1 =
275864-YIM-C-091040 Johnson Controls Unitary ProductsOptional VAV Startup and ControlFor units with VFD and VAV control, the unit must first be put in
275864-YIM-C-0910Johnson Controls Unitary Products 41room thermostat is set in the "AUTO" position) and drives the economizer dampers from f
275864-YIM-C-091042 Johnson Controls Unitary ProductsEconomizer With Optional Intelli-comfort™ With Power ExhaustThe power exhaust motor is energized
275864-YIM-C-0910Johnson Controls Unitary Products 43controlled. On any fault, only the associated system will be affected by any safety/preventive ac
275864-YIM-C-091044 Johnson Controls Unitary ProductsFigure 22: Reheat Control BoardRY1Y2GW1OCCCW2P4P5P6P3COMHGRRHGRHUMK1K2K4K3`MODESELECTIONJUMPERDEH
275864-YIM-C-0910Johnson Controls Unitary Products 45Figure 23: Reheat Controls - Part 1Figure 24: Reheat Controls - Part 2UCBUNIT CONTROLBOARDRHBREHE
275864-YIM-C-091046 Johnson Controls Unitary ProductsFigure 25: System Piping SchematicElectric Heating Sequence Of OperationsThe following sequence d
275864-YIM-C-0910Johnson Controls Unitary Products 47Electric Heat Operation ErrorsTemperature LimitIf the UCB senses zero volts from the high tempera
275864-YIM-C-091048 Johnson Controls Unitary Productsspeed of the draft motor reaches approximately 2500 RPM, the centrifugal switch contact, located
275864-YIM-C-0910Johnson Controls Unitary Products 49Safety ControlsThe UCB monitors the temperature limit switch of gas heat units.The control circui
275864-YIM-C-0910Johnson Controls Unitary Products 5InstallationInstallation Safety InformationRead these instructions before continuing this applianc
275864-YIM-C-091050 Johnson Controls Unitary ProductsStart-Up (Cooling)Prestart Check ListAfter installation has been completed:1. Check the electrica
275864-YIM-C-0910Johnson Controls Unitary Products 51Shut Down1. Set the thermostat to the lowest temperature setting.2. Turn “OFF” all electric power
275864-YIM-C-091052 Johnson Controls Unitary ProductsPilot CheckoutThe pilot flame should envelope the end of the flame sensor. To adjust pilot flame,
275864-YIM-C-0910Johnson Controls Unitary Products 53Charging The UnitFigure 31: ZR180 (15 Ton) Charging ChartFigure 32: ZR240 (20 Ton) Charging Chart
275864-YIM-C-091054 Johnson Controls Unitary ProductsFigure 33: ZR300 (25 Ton) Charging ChartTroubleshootingCooling Troubleshooting GuideOn calls for
275864-YIM-C-0910Johnson Controls Unitary Products 55action as needed. If the motor still does not operate, replace the motor.6. If 24 volts is not pr
275864-YIM-C-091056 Johnson Controls Unitary ProductsTo test, disconnect the Mate-N-Locks and jumper between the WHITE and YELLOW wires of the UCB’s M
275864-YIM-C-0910Johnson Controls Unitary Products 572. Check for line voltage at the compressor contactor, M1, and that the contactor is pulled in. C
275864-YIM-C-091058 Johnson Controls Unitary Products1. Place the thermostat fan switch in the “ON” position. If the supply air blower motor energizes
275864-YIM-C-0910Johnson Controls Unitary Products 59making good electrical connection. Check to make sure that the ceramic insulator on the pilot ign
275864-YIM-C-09106 Johnson Controls Unitary ProductsFigure 1: ZR180-300 Component LocationSimplicity® Control Board 110 Volt Convenience Outlet(“Power
275864-YIM-C-091060 Johnson Controls Unitary ProductsFigure 34: Unit Control BoardTable 26: Unit Control Board Flash CodesFLASH CODE DESCRIPTIONGREENL
Subject to change without notice. Printed in U.S.A. 275864-YIM-C-0910Copyright © 2010 by Johnson Controls, Inc. All rights reserved. Supersedes: 2758
275864-YIM-C-0910Johnson Controls Unitary Products 7LocationUse the following guidelines to select a suitable location for these units:1. Unit is desi
275864-YIM-C-09108 Johnson Controls Unitary ProductsFigure 2: Unit 4 Point Load WeightFigure 3: Unit 6 Point Load WeightFigure 4: Center of GravityAll
275864-YIM-C-0910Johnson Controls Unitary Products 9Figure 5: ZR180-300 Unit Dimensions Front ViewNote: All entry holes should be sealed to prevent ra