GENERALYORK Model DEG units are single package air conditioners withgas heat designed for outdoor installation on a rooftop or a slab.The units are co
10 Unitary Products Group035-14832-003-A-0204TABLE 7 - SUPPLY AIR PERFORMANCE - 5 Ton w/Belt-Drive BlowerMODELDEGAIR FLOWCFMAvailable External Static
Unitary Products Group 11035-14832-003-A-0204MODELDEGPOWERSUPPLYVOLTAGELIMITATIONS(SEE NOTE 1)COMPRESSORCOND.FANMOTOR,FLASUPPLYAIRBLOWERMOTOR,FLAMINIM
12 Unitary Products Group035-14832-003-A-0204FIG. 9 - DIMENSIONS AND CLEARANCES (3, 4 & 5 TON)All dimensions are in inches. They aresubject to cha
COOLING SYSTEMThe cooling section is a complete factory package utilizing anair-cooled condenser. The system is factory-charged withRefrigerant-22.The
SAFETY CONTROLS (Heating)The control circuit includes the following safety controls:1. Limit Control (LS).This control is located inside the heatexcha
PILOT CHECKOUTThe pilot flame should envelope 3/8 inches of the end of theflame sensor. Refer to Figure 12. To adjust pilot flame, (1)remove pilot adj
NOTE: The tubes must be inserted and held in a position per-pendicular to the air flow so that velocity pressure willnot affect the static pressure re
NORMAL MAINTENANCECAUTION: Prior to any of the following maintenance proce-dures, shut off all power to the unit to prevent per-sonal injury.Periodic
WARNING:Troubleshooting of components necessarily re-quires opening the electrical control box with thepower connected to the unit. Use extreme carewh
6. The pilot burner ignites but the sparker continues to sparkand the main burners do not ignite.a. Make the same checks and adjustments as describedi
035-14832-003-A-02042 Unitary Products GroupGeneral...1Inspection...
035-14832-003-A-0204Supersedes: 035-14832-002-A-0302Unitary Products Group5005 York Drive, Norman Oklahoma 73069Subject to change without notice. Pr
LIMITATIONSThese units must be installed in accordance with the currentedition of the following national and local safety codes:In the U.S.A.:1. Natio
The supply and return air duct systems should be designed for theCFM and static requirements of the job. They should NOTbesized to match the dimension
DISCONNECT SWITCH BRACKET FOR UNITSWITH OPTIONAL BELT-DRIVE BRACKETA special bracket for mounting a field-supplied disconnectswitch is provided in eac
GAS CONNECTIONThe gas supply line can be routed through the knockoutslocated on the front of the unit or through the opening providedin the unit'
VENT AND COMBUSTION AIR HOODSThe vent and combustion air hoods are shipped attached to theblower housing in the blower compartment. These hoods mustbe
NOTE: Install filters so that “Air Flow” arrows point toward theunit.8. Install filter cover over the end of the hood with one screw(center of hood),